Motor FLA Chart – NEC Full-Load Current Tables

Full-load amps for single-phase and three-phase motors per NEC Tables 430.248 and 430.250, from 1/6 HP through 200 HP at 115V, 208V, 230V, 460V, and 575V.

Why the NEC Table Values Matter

NEC 430.6(A)(1) requires you to use the full-load current values from the NEC tables — not the motor nameplate amps — when sizing conductors, disconnecting means, and branch-circuit short-circuit and ground-fault protection. The tables provide standardized values so circuits are sized consistently, even if a specific motor draws slightly more or less current than average.

The nameplate current rating is used for one thing only: sizing the motor's separate overload protection per NEC 430.32. Everything else in the motor circuit — wire, breaker or fuses, and disconnect — is sized from the table FLA.

Single-phase AC motor currents come from NEC Table 430.248, and three-phase AC induction motor currents come from NEC Table 430.250. Both tables below list the standard values used in the field. Note that the tables use motor utilization voltages: a 460V motor runs on a 480V system, a 230V motor on a 240V system, and a 115V motor on a 120V system.

Tip: If your motor's horsepower or voltage isn't listed, or you need starting current, use our HP to amps calculator or motor starting calculator.

Single-Phase Motor FLA — NEC Table 430.248

Full-load currents in amperes for single-phase alternating-current motors running at usual speeds and with normal torque characteristics

Horsepower115 Volts230 Volts
1/6 HP4.4 A2.2 A
1/4 HP5.8 A2.9 A
1/3 HP7.2 A3.6 A
1/2 HP9.8 A4.9 A
3/4 HP13.8 A6.9 A
1 HP16 A8 A
1-1/2 HP20 A10 A
2 HP24 A12 A
3 HP34 A17 A
5 HP56 A28 A
7-1/2 HP80 A40 A
10 HP100 A50 A

Values assume motors running at usual speeds with normal torque characteristics. For 120V and 240V systems, use the 115V and 230V columns respectively.

Three-Phase Motor FLA — NEC Table 430.250

Full-load currents in amperes for three-phase alternating-current induction motors (squirrel-cage and wound-rotor) running at usual speeds with normal torque characteristics

Horsepower208 Volts230 Volts460 Volts575 Volts
1/2 HP2.4 A2.2 A1.1 A0.9 A
3/4 HP3.5 A3.2 A1.6 A1.3 A
1 HP4.6 A4.2 A2.1 A1.7 A
1-1/2 HP6.6 A6.0 A3.0 A2.4 A
2 HP7.5 A6.8 A3.4 A2.7 A
3 HP10.6 A9.6 A4.8 A3.9 A
5 HP16.7 A15.2 A7.6 A6.1 A
7-1/2 HP24.2 A22 A11 A9 A
10 HP30.8 A28 A14 A11 A
15 HP46.2 A42 A21 A17 A
20 HP59.4 A54 A27 A22 A
25 HP74.8 A68 A34 A27 A
30 HP88 A80 A40 A32 A
40 HP114 A104 A52 A41 A
50 HP143 A130 A65 A52 A
60 HP169 A154 A77 A62 A
75 HP211 A192 A96 A77 A
100 HP273 A248 A124 A99 A
125 HP343 A312 A156 A125 A
150 HP396 A360 A180 A144 A
200 HP528 A480 A240 A192 A

Use the 460V column for motors on 480V systems and the 575V column for motors on 600V systems. NEC Table 430.250 continues through 500 HP; the values above cover the sizes most commonly installed.

How to Use FLA Tables for Circuit Sizing

1

Look up the table FLA

Find your motor's horsepower and voltage in Table 430.248 (single-phase) or 430.250 (three-phase) above. Use this value — not the nameplate amps — per NEC 430.6(A)(1).

2

Size the conductors at 125% of FLA

NEC 430.22 requires branch-circuit conductors supplying a single continuous-duty motor to have an ampacity of at least 125% of the table FLA. Then pick the wire from the ampacity table using our wire sizing calculator.

3

Size the branch-circuit protection per NEC 430.52

Motor branch-circuit short-circuit protection is sized as a percentage of table FLA from Table 430.52 — up to 250% of FLA for an inverse-time circuit breaker (175% for dual-element time-delay fuses). This allows the breaker to hold in during motor starting inrush; the separate overload device protects against sustained overcurrent.

4

Size the overloads from the nameplate

Overload protection is based on the actual nameplate current rating per NEC 430.32 — typically 125% for motors with a service factor of 1.15 or more, or 115% for all others.

Worked example: A 10 HP, 460V three-phase motor has a table FLA of 14 A (Table 430.250). Minimum conductor ampacity = 14 × 1.25 = 17.5 A → #12 THWN copper (25 A at 75°C). Maximum inverse-time breaker = 14 × 2.50 = 35 A. So a typical installation uses #12 copper conductors on a 35 A breaker with overloads set from the nameplate amps.

Frequently Asked Questions

What is motor FLA?

Motor FLA (full-load amps) is the current a motor draws when operating at its rated horsepower, voltage, and speed. For sizing conductors, disconnects, and branch-circuit protection, NEC 430.6(A)(1) requires using the FLA values from NEC Tables 430.247 through 430.250 — not the amps printed on the motor nameplate. The nameplate current is used only for sizing overload protection per NEC 430.32.

How many amps does a 5 HP motor draw?

A 5 HP single-phase motor draws 56 amps at 115V or 28 amps at 230V per NEC Table 430.248. A 5 HP three-phase motor draws 16.7 amps at 208V, 15.2 amps at 230V, 7.6 amps at 460V, or 6.1 amps at 575V per NEC Table 430.250. Three-phase motors draw far less current per horsepower, which is why larger motors are almost always three-phase.

Do I use nameplate amps or table amps?

Use the NEC table amps for sizing conductors, disconnecting means, and branch-circuit short-circuit protection — NEC 430.6(A)(1) requires it, even when the nameplate shows a different value. Use the nameplate amps only for sizing the motor's overload protection per NEC 430.32, because overloads protect the specific motor as built, while conductors and breakers are sized from the standardized table values.

What NEC table lists three-phase motor full-load current?

NEC Table 430.250 lists full-load currents for three-phase alternating-current motors (squirrel-cage and wound-rotor induction) from 1/2 HP through 500 HP at 115V, 200V, 208V, 230V, 460V, 575V, and 2,300V. For single-phase AC motors, use NEC Table 430.248; for DC motors, Table 430.247; and for two-phase motors, Table 430.249.

Why does the FLA table show 460V instead of 480V?

The NEC motor tables list motor utilization voltages, not nominal system voltages. A motor connected to a 480V distribution system is rated 460V to allow for voltage drop between the service and the motor terminals. The same applies to 115V motors on 120V systems, 230V motors on 240V systems, and 575V motors on 600V systems. For a 480V system, use the 460V column.

Related Electrical Calculators

Motor Starting Calculator

Calculate motor starting current, inrush, and voltage dip for any motor size.

Calculate Motor Starting →

HP to Amps Calculator

Convert horsepower to amps for any voltage, phase, efficiency, and power factor.

Convert HP to Amps →

Wire Sizing Calculator

Find the correct wire gauge for 125% of motor FLA per NEC ampacity tables.

Calculate Wire Size →

Breaker Size Calculator

Determine the right breaker size for motor and non-motor loads.

Calculate Breaker Size →