Wire Ampacity Chart (NEC Table 310.16)
Complete ampacity table based on NEC Table 310.16 (formerly 310.15(B)(16)). Allowable ampacities for copper and aluminum conductors at 60°C, 75°C, and 90°C, from 14 AWG through 2000 kcmil.
What Is Wire Ampacity?
Ampacity is the maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.The word “ampacity” combines “ampere” and “capacity.”
NEC Table 310.16 is the most referenced table in electrical work. It lists allowable ampacities for insulated conductors rated up to 2000 volts, in raceways, cables, or direct-buried, based on an ambient temperature of 86°F (30°C) with no more than 3 current-carrying conductors in a raceway.
The ampacity depends on four factors: wire gauge (AWG/kcmil), conductor material (copper vs. aluminum), insulation temperature rating (60°C, 75°C, or 90°C), and installation conditions (ambient temperature and number of conductors in a raceway).
Important:Even when using 90°C-rated wire (THHN, XHHW-2), you must use the ampacity from the column matching the lowest temperature-rated component in the circuit — usually the terminals, which are typically rated 60°C or 75°C. See NEC 110.14(C).
Copper Conductor Ampacity — NEC Table 310.16 (formerly 310.15(B)(16))
NEC Table 310.16 (formerly 310.15(B)(16)) — based on ambient temperature of 86°F (30°C), ≤3 current-carrying conductors in raceway or cable
| Wire Size | 60°C TW, UF | 75°C THW, THWN, XHHW | 90°C THHN, THWN-2, XHHW-2 | Typical Breaker |
|---|---|---|---|---|
| 14 AWG | 15A | 20A | 25A | 15A |
| 12 AWG | 20A | 25A | 30A | 20A |
| 10 AWG | 30A | 35A | 40A | 30A |
| 8 AWG | 40A | 50A | 55A | 40A |
| 6 AWG | 55A | 65A | 75A | 60A |
| 4 AWG | 70A | 85A | 95A | 70A |
| 3 AWG | 85A | 100A | 115A | 100A |
| 2 AWG | 95A | 115A | 130A | 100A |
| 1 AWG | 110A | 130A | 145A | 110A |
| 1/0 AWG | 125A | 150A | 170A | 150A |
| 2/0 AWG | 145A | 175A | 195A | 175A |
| 3/0 AWG | 165A | 200A | 225A | 200A |
| 4/0 AWG | 195A | 230A | 260A | 200A |
| 250 kcmil | 215A | 255A | 290A | — |
| 300 kcmil | 240A | 285A | 320A | — |
| 350 kcmil | 260A | 310A | 350A | — |
| 400 kcmil | 280A | 335A | 380A | — |
| 500 kcmil | 320A | 380A | 430A | — |
| 600 kcmil | 355A | 420A | 475A | — |
| 700 kcmil | 385A | 460A | 520A | — |
| 750 kcmil | 400A | 475A | 535A | — |
| 800 kcmil | 410A | 490A | 555A | — |
| 900 kcmil | 435A | 520A | 585A | — |
| 1000 kcmil | 455A | 545A | 615A | — |
| 1250 kcmil | 495A | 590A | 665A | — |
| 1500 kcmil | 525A | 625A | 705A | — |
| 1750 kcmil | 545A | 650A | 735A | — |
| 2000 kcmil | 555A | 665A | 750A | — |
Aluminum Conductor Ampacity — NEC Table 310.16 (formerly 310.15(B)(16))
NEC Table 310.16 (formerly 310.15(B)(16)) — based on ambient temperature of 86°F (30°C), ≤3 current-carrying conductors in raceway or cable
| Wire Size | 60°C TW, UF | 75°C THW, THWN, XHHW | 90°C THHN, THWN-2, XHHW-2 |
|---|---|---|---|
| 12 AWG | 15A | 20A | 25A |
| 10 AWG | 25A | 30A | 35A |
| 8 AWG | 35A | 40A | 45A |
| 6 AWG | 40A | 50A | 55A |
| 4 AWG | 55A | 65A | 75A |
| 3 AWG | 65A | 75A | 85A |
| 2 AWG | 75A | 90A | 100A |
| 1 AWG | 85A | 100A | 115A |
| 1/0 AWG | 100A | 120A | 135A |
| 2/0 AWG | 115A | 135A | 150A |
| 3/0 AWG | 130A | 155A | 175A |
| 4/0 AWG | 150A | 180A | 205A |
| 250 kcmil | 170A | 205A | 230A |
| 300 kcmil | 195A | 230A | 260A |
| 350 kcmil | 210A | 250A | 280A |
| 400 kcmil | 225A | 270A | 305A |
| 500 kcmil | 260A | 310A | 350A |
| 600 kcmil | 285A | 340A | 385A |
| 700 kcmil | 315A | 375A | 425A |
| 750 kcmil | 320A | 385A | 435A |
| 800 kcmil | 330A | 395A | 445A |
| 900 kcmil | 355A | 425A | 480A |
| 1000 kcmil | 375A | 445A | 500A |
| 1250 kcmil | 405A | 485A | 545A |
| 1500 kcmil | 435A | 520A | 585A |
| 1750 kcmil | 455A | 545A | 615A |
| 2000 kcmil | 470A | 560A | 630A |
Note: Aluminum wire requires special installation practices. Use anti-oxidant compound on all connections, torque terminals to manufacturer specifications, and only use connectors rated for aluminum (marked AL or AL/CU). NEC 14 AWG aluminum is not commonly available and is rarely used.
Temperature Correction Factors (NEC 310.15(B)(1))
NEC Table 310.15(B)(1)(1), based on a 30°C (86°F) ambient — multiply the ampacity from Table 310.16 by this factor when the ambient temperature differs from 86°F (30°C)
| Ambient Temperature | 60°C Wire | 75°C Wire | 90°C Wire |
|---|---|---|---|
| 70–77°F (21–25°C) | 1.08 | 1.05 | 1.04 |
| 78–86°F (26–30°C) | 1 | 1 | 1 |
| 87–95°F (31–35°C) | 0.91 | 0.94 | 0.96 |
| 96–104°F (36–40°C) | 0.82 | 0.88 | 0.91 |
| 105–113°F (41–45°C) | 0.71 | 0.82 | 0.87 |
| 114–122°F (46–50°C) | 0.58 | 0.75 | 0.82 |
| 123–131°F (51–55°C) | 0.41 | 0.67 | 0.76 |
| 132–140°F (56–60°C) | — | 0.58 | 0.71 |
| 141–149°F (61–65°C) | — | 0.47 | 0.65 |
| 150–158°F (66–70°C) | — | 0.33 | 0.58 |
Example: 6 AWG THWN copper in a 104°F (40°C) attic. Base ampacity = 65A (75°C column). Temperature factor = 0.88. Derated ampacity = 65 × 0.88 = 57.2A.
Conduit Fill Adjustment Factors — NEC 310.15(C)(1)
Reduce ampacity when more than 3 current-carrying conductors are in the same raceway or cable
| Number of Conductors | Percent of Ampacity | Multiplier |
|---|---|---|
| 1–3 | 100% | 1.00 |
| 4–6 | 80% | 0.80 |
| 7–9 | 70% | 0.70 |
| 10–20 | 50% | 0.50 |
| 21–30 | 45% | 0.45 |
| 31–40 | 40% | 0.40 |
| 41+ | 35% | 0.35 |
Example: Six 12 AWG THHN conductors in one conduit (6 current-carrying conductors). Base ampacity = 30A (90°C column for derating purposes). Conduit fill factor = 0.80. Derated ampacity = 30 × 0.80 = 24A. Since the 75°C column value is 25A, the final ampacity is 24A.
How to Use Table 310.16
Determine the load current
Calculate the full-load amperage of your circuit. Use our amps to watts calculator or Ohm's Law calculator if needed.
Identify the temperature column
Pick the column matching both the wire insulation rating AND the termination rating per NEC 110.14(C) — use the lower of the two. Most modern breaker and panel terminations are rated 75°C; equipment rated 100A or less may be limited to 60°C.
Find the wire size
Look up the ampacity in the correct column. Select a wire with ampacity equal to or greater than your load current. Use our wire sizing calculator for automated results.
Apply derating if needed
If ambient temperature exceeds 86°F or there are more than 3 conductors in a raceway, apply the correction factors above. You may use the 90°C column as the starting point for derating calculations.
Check voltage drop
For long runs, verify that voltage drop stays within NEC recommendations (3% branch, 5% total). You may need to upsize the wire.
Common Wire Sizes: Quick Reference
Residential (Copper)
- 14 AWG — 15A breaker, lighting circuits
- 12 AWG — 20A breaker, general receptacles, kitchen
- 10 AWG — 30A breaker, dryers, water heaters
- 8 AWG — 40A breaker, cooktops, large A/C
- 6 AWG — 60A breaker, sub-panels, large EV chargers
- 4 AWG — 70A breaker, sub-panels
- 2 AWG — 100A sub-panel feeders
- 4/0 AWG — 200A service entrance
Commercial / Aluminum
- 1/0 AL — 100A service (residential)
- 4/0 AL — 200A service (residential)
- 250 kcmil AL — 200A feeders
- 350 kcmil AL — 250A feeders
- 500 kcmil AL — 300A feeders
- 750 kcmil AL — 400A services
- Parallel runs — 2+ sets for >500A
Frequently Asked Questions
What is NEC Table 310.16?
NEC Table 310.16 (formerly Table 310.15(B)(16)) is the National Electrical Code's ampacity table for insulated conductors rated up to 2000 volts installed in raceways, cables, or directly buried. It lists allowable ampacities for copper and aluminum conductors at 60°C, 75°C, and 90°C insulation ratings, based on a 30°C (86°F) ambient with no more than 3 current-carrying conductors. It is the starting point for nearly every wire sizing calculation.
What is wire ampacity?
Wire ampacity is the maximum amount of electrical current a conductor can carry continuously without exceeding its temperature rating. Ampacity depends on the wire gauge (size), insulation type, ambient temperature, and the number of current-carrying conductors in a raceway. NEC Table 310.16 lists standard ampacity values.
What is the ampacity of 12 AWG copper wire?
12 AWG copper wire has an ampacity of 20 amps at 60°C (TW), 25 amps at 75°C (THWN), and 30 amps at 90°C (THHN, THWN-2). However, NEC 240.4(D) limits 12 AWG copper to a 20-amp overcurrent device regardless of the column used, which is why 12 AWG is installed on 20-amp breakers.
What size wire do I need for 100 amps?
For 100 amps, you typically need 1 AWG copper (130A at 75°C) or 1/0 AWG aluminum (120A at 75°C). For a 100-amp service entrance, NEC 230.79 requires a minimum of 1 AWG copper or 1/0 aluminum. Always check local codes and consider voltage drop for long runs.
What is temperature derating?
Temperature derating reduces the ampacity of a wire when the ambient temperature exceeds 86°F (30°C). For example, in a 104°F (40°C) environment, a 75°C-rated conductor's ampacity is multiplied by 0.88, reducing it by 12%. This is required by NEC 310.15(B)(1).
What is conduit fill derating?
When more than 3 current-carrying conductors are installed in a raceway, the ampacity must be reduced per NEC 310.15(C)(1). For 4–6 conductors, ampacity drops to 80%. For 7–9 conductors, 70%. This is because more conductors generate more heat in a confined space.
Do I use the 75°C or 90°C column?
In most cases, use the 75°C column. Per NEC 110.14(C), conductor ampacity is limited by the temperature rating of the terminations, and most modern breakers, panels, and equipment terminals are rated 75°C (equipment rated 100A or less may be rated only 60°C). The 90°C column is mainly used as the starting ampacity for applying correction and adjustment factors — the final derated value still cannot exceed the 75°C (or 60°C) termination rating.
Can I use the 90°C ampacity column for wire sizing?
Generally no — you must size wire based on the temperature rating of the lowest-rated component (usually the terminal). However, per NEC 310.15(B)(1), you CAN use the 90°C column as a starting point for derating calculations, then verify the final ampacity doesn't exceed the 60°C or 75°C column value.
What is the difference between 60°C, 75°C, and 90°C wire ratings?
These ratings indicate the maximum temperature the wire insulation can handle. 60°C (TW, UF) is basic. 75°C (THW, THWN) is most common for commercial work. 90°C (THHN, THWN-2) allows the highest ampacity but is limited by terminal ratings — most equipment is rated 60°C or 75°C.
Related Electrical Calculators
Wire Sizing Calculator
Automatically calculate the correct wire gauge based on amperage, distance, and voltage.
Calculate Wire Size →Voltage Drop Calculator
Calculate voltage drop for any wire size and distance to meet NEC recommendations.
Calculate Voltage Drop →Conduit Fill Calculator
Calculate conduit fill percentage per NEC Chapter 9 tables for any conduit type.
Calculate Conduit Fill →Breaker Size Calculator
Determine the right breaker size for your wire gauge and load type.
Calculate Breaker Size →Ohm's Law Calculator
Calculate voltage, current, resistance, and power using Ohm's Law formulas.
Calculate Ohm's Law →Load Calculation Calculator
Calculate total electrical load for service sizing per NEC Article 220.
Calculate Loads →Wire Size Chart by Amps
Quick wire size answers for common 30-200A circuits, from dryers to 200 amp services.
View Wire Size Chart →AWG to mm² Converter
Convert AWG wire gauges to metric cross-sections when comparing ampacity across standards.
Convert AWG to mm² →