Wire Ampacity Chart (NEC Table 310.16)

Complete ampacity table based on NEC Table 310.16 (formerly 310.15(B)(16)). Allowable ampacities for copper and aluminum conductors at 60°C, 75°C, and 90°C, from 14 AWG through 2000 kcmil.

What Is Wire Ampacity?

Ampacity is the maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.The word “ampacity” combines “ampere” and “capacity.”

NEC Table 310.16 is the most referenced table in electrical work. It lists allowable ampacities for insulated conductors rated up to 2000 volts, in raceways, cables, or direct-buried, based on an ambient temperature of 86°F (30°C) with no more than 3 current-carrying conductors in a raceway.

The ampacity depends on four factors: wire gauge (AWG/kcmil), conductor material (copper vs. aluminum), insulation temperature rating (60°C, 75°C, or 90°C), and installation conditions (ambient temperature and number of conductors in a raceway).

Important:Even when using 90°C-rated wire (THHN, XHHW-2), you must use the ampacity from the column matching the lowest temperature-rated component in the circuit — usually the terminals, which are typically rated 60°C or 75°C. See NEC 110.14(C).

Copper Conductor Ampacity — NEC Table 310.16 (formerly 310.15(B)(16))

NEC Table 310.16 (formerly 310.15(B)(16)) — based on ambient temperature of 86°F (30°C), ≤3 current-carrying conductors in raceway or cable

Wire Size60°C
TW, UF
75°C
THW, THWN, XHHW
90°C
THHN, THWN-2, XHHW-2
Typical Breaker
14 AWG15A20A25A15A
12 AWG20A25A30A20A
10 AWG30A35A40A30A
8 AWG40A50A55A40A
6 AWG55A65A75A60A
4 AWG70A85A95A70A
3 AWG85A100A115A100A
2 AWG95A115A130A100A
1 AWG110A130A145A110A
1/0 AWG125A150A170A150A
2/0 AWG145A175A195A175A
3/0 AWG165A200A225A200A
4/0 AWG195A230A260A200A
250 kcmil215A255A290A—
300 kcmil240A285A320A—
350 kcmil260A310A350A—
400 kcmil280A335A380A—
500 kcmil320A380A430A—
600 kcmil355A420A475A—
700 kcmil385A460A520A—
750 kcmil400A475A535A—
800 kcmil410A490A555A—
900 kcmil435A520A585A—
1000 kcmil455A545A615A—
1250 kcmil495A590A665A—
1500 kcmil525A625A705A—
1750 kcmil545A650A735A—
2000 kcmil555A665A750A—

Aluminum Conductor Ampacity — NEC Table 310.16 (formerly 310.15(B)(16))

NEC Table 310.16 (formerly 310.15(B)(16)) — based on ambient temperature of 86°F (30°C), ≤3 current-carrying conductors in raceway or cable

Wire Size60°C
TW, UF
75°C
THW, THWN, XHHW
90°C
THHN, THWN-2, XHHW-2
12 AWG15A20A25A
10 AWG25A30A35A
8 AWG35A40A45A
6 AWG40A50A55A
4 AWG55A65A75A
3 AWG65A75A85A
2 AWG75A90A100A
1 AWG85A100A115A
1/0 AWG100A120A135A
2/0 AWG115A135A150A
3/0 AWG130A155A175A
4/0 AWG150A180A205A
250 kcmil170A205A230A
300 kcmil195A230A260A
350 kcmil210A250A280A
400 kcmil225A270A305A
500 kcmil260A310A350A
600 kcmil285A340A385A
700 kcmil315A375A425A
750 kcmil320A385A435A
800 kcmil330A395A445A
900 kcmil355A425A480A
1000 kcmil375A445A500A
1250 kcmil405A485A545A
1500 kcmil435A520A585A
1750 kcmil455A545A615A
2000 kcmil470A560A630A

Note: Aluminum wire requires special installation practices. Use anti-oxidant compound on all connections, torque terminals to manufacturer specifications, and only use connectors rated for aluminum (marked AL or AL/CU). NEC 14 AWG aluminum is not commonly available and is rarely used.

Temperature Correction Factors (NEC 310.15(B)(1))

NEC Table 310.15(B)(1)(1), based on a 30°C (86°F) ambient — multiply the ampacity from Table 310.16 by this factor when the ambient temperature differs from 86°F (30°C)

Ambient Temperature60°C Wire75°C Wire90°C Wire
70–77°F (21–25°C)1.081.051.04
78–86°F (26–30°C)111
87–95°F (31–35°C)0.910.940.96
96–104°F (36–40°C)0.820.880.91
105–113°F (41–45°C)0.710.820.87
114–122°F (46–50°C)0.580.750.82
123–131°F (51–55°C)0.410.670.76
132–140°F (56–60°C)—0.580.71
141–149°F (61–65°C)—0.470.65
150–158°F (66–70°C)—0.330.58

Example: 6 AWG THWN copper in a 104°F (40°C) attic. Base ampacity = 65A (75°C column). Temperature factor = 0.88. Derated ampacity = 65 × 0.88 = 57.2A.

Conduit Fill Adjustment Factors — NEC 310.15(C)(1)

Reduce ampacity when more than 3 current-carrying conductors are in the same raceway or cable

Number of ConductorsPercent of AmpacityMultiplier
1–3100%1.00
4–680%0.80
7–970%0.70
10–2050%0.50
21–3045%0.45
31–4040%0.40
41+35%0.35

Example: Six 12 AWG THHN conductors in one conduit (6 current-carrying conductors). Base ampacity = 30A (90°C column for derating purposes). Conduit fill factor = 0.80. Derated ampacity = 30 × 0.80 = 24A. Since the 75°C column value is 25A, the final ampacity is 24A.

How to Use Table 310.16

1

Determine the load current

Calculate the full-load amperage of your circuit. Use our amps to watts calculator or Ohm's Law calculator if needed.

2

Identify the temperature column

Pick the column matching both the wire insulation rating AND the termination rating per NEC 110.14(C) — use the lower of the two. Most modern breaker and panel terminations are rated 75°C; equipment rated 100A or less may be limited to 60°C.

3

Find the wire size

Look up the ampacity in the correct column. Select a wire with ampacity equal to or greater than your load current. Use our wire sizing calculator for automated results.

4

Apply derating if needed

If ambient temperature exceeds 86°F or there are more than 3 conductors in a raceway, apply the correction factors above. You may use the 90°C column as the starting point for derating calculations.

5

Check voltage drop

For long runs, verify that voltage drop stays within NEC recommendations (3% branch, 5% total). You may need to upsize the wire.

Common Wire Sizes: Quick Reference

Residential (Copper)

  • 14 AWG — 15A breaker, lighting circuits
  • 12 AWG — 20A breaker, general receptacles, kitchen
  • 10 AWG — 30A breaker, dryers, water heaters
  • 8 AWG — 40A breaker, cooktops, large A/C
  • 6 AWG — 60A breaker, sub-panels, large EV chargers
  • 4 AWG — 70A breaker, sub-panels
  • 2 AWG — 100A sub-panel feeders
  • 4/0 AWG — 200A service entrance

Commercial / Aluminum

  • 1/0 AL — 100A service (residential)
  • 4/0 AL — 200A service (residential)
  • 250 kcmil AL — 200A feeders
  • 350 kcmil AL — 250A feeders
  • 500 kcmil AL — 300A feeders
  • 750 kcmil AL — 400A services
  • Parallel runs — 2+ sets for >500A

Frequently Asked Questions

What is NEC Table 310.16?

NEC Table 310.16 (formerly Table 310.15(B)(16)) is the National Electrical Code's ampacity table for insulated conductors rated up to 2000 volts installed in raceways, cables, or directly buried. It lists allowable ampacities for copper and aluminum conductors at 60°C, 75°C, and 90°C insulation ratings, based on a 30°C (86°F) ambient with no more than 3 current-carrying conductors. It is the starting point for nearly every wire sizing calculation.

What is wire ampacity?

Wire ampacity is the maximum amount of electrical current a conductor can carry continuously without exceeding its temperature rating. Ampacity depends on the wire gauge (size), insulation type, ambient temperature, and the number of current-carrying conductors in a raceway. NEC Table 310.16 lists standard ampacity values.

What is the ampacity of 12 AWG copper wire?

12 AWG copper wire has an ampacity of 20 amps at 60°C (TW), 25 amps at 75°C (THWN), and 30 amps at 90°C (THHN, THWN-2). However, NEC 240.4(D) limits 12 AWG copper to a 20-amp overcurrent device regardless of the column used, which is why 12 AWG is installed on 20-amp breakers.

What size wire do I need for 100 amps?

For 100 amps, you typically need 1 AWG copper (130A at 75°C) or 1/0 AWG aluminum (120A at 75°C). For a 100-amp service entrance, NEC 230.79 requires a minimum of 1 AWG copper or 1/0 aluminum. Always check local codes and consider voltage drop for long runs.

What is temperature derating?

Temperature derating reduces the ampacity of a wire when the ambient temperature exceeds 86°F (30°C). For example, in a 104°F (40°C) environment, a 75°C-rated conductor's ampacity is multiplied by 0.88, reducing it by 12%. This is required by NEC 310.15(B)(1).

What is conduit fill derating?

When more than 3 current-carrying conductors are installed in a raceway, the ampacity must be reduced per NEC 310.15(C)(1). For 4–6 conductors, ampacity drops to 80%. For 7–9 conductors, 70%. This is because more conductors generate more heat in a confined space.

Do I use the 75°C or 90°C column?

In most cases, use the 75°C column. Per NEC 110.14(C), conductor ampacity is limited by the temperature rating of the terminations, and most modern breakers, panels, and equipment terminals are rated 75°C (equipment rated 100A or less may be rated only 60°C). The 90°C column is mainly used as the starting ampacity for applying correction and adjustment factors — the final derated value still cannot exceed the 75°C (or 60°C) termination rating.

Can I use the 90°C ampacity column for wire sizing?

Generally no — you must size wire based on the temperature rating of the lowest-rated component (usually the terminal). However, per NEC 310.15(B)(1), you CAN use the 90°C column as a starting point for derating calculations, then verify the final ampacity doesn't exceed the 60°C or 75°C column value.

What is the difference between 60°C, 75°C, and 90°C wire ratings?

These ratings indicate the maximum temperature the wire insulation can handle. 60°C (TW, UF) is basic. 75°C (THW, THWN) is most common for commercial work. 90°C (THHN, THWN-2) allows the highest ampacity but is limited by terminal ratings — most equipment is rated 60°C or 75°C.

Related Electrical Calculators

Wire Sizing Calculator

Automatically calculate the correct wire gauge based on amperage, distance, and voltage.

Calculate Wire Size →

Voltage Drop Calculator

Calculate voltage drop for any wire size and distance to meet NEC recommendations.

Calculate Voltage Drop →

Conduit Fill Calculator

Calculate conduit fill percentage per NEC Chapter 9 tables for any conduit type.

Calculate Conduit Fill →

Breaker Size Calculator

Determine the right breaker size for your wire gauge and load type.

Calculate Breaker Size →

Ohm's Law Calculator

Calculate voltage, current, resistance, and power using Ohm's Law formulas.

Calculate Ohm's Law →

Load Calculation Calculator

Calculate total electrical load for service sizing per NEC Article 220.

Calculate Loads →

Wire Size Chart by Amps

Quick wire size answers for common 30-200A circuits, from dryers to 200 amp services.

View Wire Size Chart →

AWG to mm² Converter

Convert AWG wire gauges to metric cross-sections when comparing ampacity across standards.

Convert AWG to mm² →