NEC Code Quick Reference Guide

A quick-reference guide to the most commonly cited National Electrical Code (NEC) articles. Built for electricians, inspectors, and electrical engineers who need to look up code sections fast — with links to the calculators that put them into practice.

What Is the NEC?

The National Electrical Code (NFPA 70) is the benchmark for safe electrical design, installation, and inspection in the United States. Published by the National Fire Protection Association (NFPA), the NEC is updated on a three-year cycle — the current edition is NEC 2023.

Most states adopt the NEC as law, sometimes with local amendments. Whether you're pulling a permit, studying for a journeyman exam, or designing a commercial installation, knowing which NEC article applies is the first step to getting it right.

Most-Used NEC Articles — Quick Reference

ArticleTitleWhat It CoversRelated Calculator
90IntroductionScope, purpose, enforcement of the NEC
100DefinitionsTerms used throughout the NEC
110Requirements for Electrical InstallationsWorking space, terminal ratings (110.14), conductor termination temperatures
210Branch CircuitsBranch circuit ratings, GFCI/AFCI requirements, outlet spacingBranch Circuit Calculator
215FeedersFeeder sizing, voltage drop considerationsVoltage Drop Calculator
220Branch-Circuit, Feeder, and Service Load CalculationsDemand factors, load calculations, dwelling unit calculationsLoad Calculation Calculator
225Outside Branch Circuits and FeedersOutside feeders, clearances
230ServicesService entrance conductors, disconnects, overcurrent protectionService Entrance Calculator
240Overcurrent ProtectionBreaker and fuse sizing, tap rulesBreaker Size Calculator
250Grounding and BondingEquipment grounding, grounding electrode system, bondingGrounding Calculator
300General Requirements for Wiring MethodsConductor routing, conduit requirements, underground wiringConduit Fill Calculator
310Conductors for General WiringWire ampacity (Table 310.16), temperature ratings, deratingWire Ampacity Chart
314Outlet, Device, Pull, and Junction BoxesBox fill calculations, box sizing
334Nonmetallic-Sheathed Cable (NM/Romex)NM cable installation, permitted uses, securing requirements
344–362Raceways (EMT, IMC, RMC, PVC, etc.)Conduit types, fill limits, support spacingConduit Fill Calculator
404SwitchesSwitch connections, grounding requirements
406Receptacles, Cord Connectors, and Attachment PlugsReceptacle ratings, tamper-resistant requirements
408Switchboards, Panelboards, and Distribution BoardsPanel schedules, clearances, labelingPanel Schedule Calculator
410Luminaires, Lampholders, and LampsLighting fixture installation, clearancesLighting Calculator
422AppliancesAppliance circuits, disconnects
424Fixed Electric Space-Heating EquipmentBaseboard heaters, unit heaters, duct heaters
430Motors, Motor Circuits, and ControllersMotor FLC, overload protection, conductor sizingMotor Starting Calculator
440Air-Conditioning and Refrigerating EquipmentA/C circuit sizing, disconnects
445GeneratorsGenerator conductor sizing, disconnects, groundingGenerator Sizing Calculator
480Batteries and Battery SystemsBattery room requirements, disconnect requirements
690Solar Photovoltaic SystemsPV system wiring, grounding, disconnects, rapid shutdownSolar System Calculator
700Emergency SystemsEmergency power wiring, transfer switches, selective coordinationEmergency System Calculator
705Interconnected Electric Power Production SourcesUtility interconnection, backfeed protection
Ch. 9TablesConduit fill areas, conductor properties, wire areasConduit Fill Calculator

NEC Key Tables You Should Know

Table 210.21(B)(3)

Receptacle ratings for various circuit sizes (e.g., 15A receptacle on a 20A circuit).

Table 220.12

General lighting loads by occupancy type (VA per square foot).

Table 250.66

Grounding electrode conductor sizing based on largest service-entrance conductor.

Table 250.122

Minimum equipment grounding conductor sizing based on overcurrent device rating.

Table 310.16

Conductor ampacity — the most referenced table in the entire NEC. View Ampacity Chart →

Table 314.16(A)

Metal box fill — maximum number of conductors allowed per box size.

Table 430.250

Motor full-load currents for three-phase motors at various voltages.

Table 430.248

Motor full-load currents for single-phase motors at various voltages.

Chapter 9, Table 1

Conduit fill percentages — 40% for 2+ conductors, 53% for 1 conductor. Conduit Fill Calculator →

Chapter 9, Table 4

Conduit dimensions and internal areas for each raceway type (EMT, IMC, RMC, PVC).

Chapter 9, Table 5

Wire cross-sectional areas (including insulation) used for conduit fill calculations. Conduit Fill Calculator →

Frequently Asked Questions

What is the current NEC edition?

The current edition is NEC 2023 (NFPA 70-2023). The National Electrical Code is updated on a 3-year cycle. Some states and jurisdictions still enforce older editions such as NEC 2020 or NEC 2017, so always check which edition your local authority having jurisdiction (AHJ) has adopted.

Is the NEC a law?

The NEC itself is a standard published by the National Fire Protection Association (NFPA), not a law. However, most states and municipalities adopt it — sometimes with local amendments — as part of their building codes, making it legally enforceable. Always verify which edition and amendments apply in your jurisdiction.

What is NEC Table 310.16?

Table 310.16 is the most referenced table in the NEC. It lists allowable ampacities for insulated conductors rated 0–2000 volts installed in raceways, cables, or direct-buried, based on a 30°C (86°F) ambient temperature with no more than 3 current-carrying conductors in a raceway or cable. Ampacity must be derated for higher temperatures or more conductors.

What NEC article covers grounding?

Article 250 covers all grounding and bonding requirements in the NEC, including equipment grounding conductors, grounding electrode systems, bonding of services, and grounding of separately derived systems.

What is the NEC 80% rule?

NEC 210.20(A) and 215.3 require that where a branch circuit or feeder supplies continuous loads (loads expected to run for 3 hours or more), the overcurrent device rating must be not less than 125% of the continuous load. In practice, this means a continuous load must not exceed 80% of the breaker rating. For example, a 20A breaker should carry no more than 16A of continuous load.

How often is the NEC updated?

The NEC is updated every 3 years. Recent editions include NEC 2017, NEC 2020, and NEC 2023. The next edition will be NEC 2026. Each new cycle incorporates changes based on public proposals, public comments, and committee actions to improve electrical safety.

Related Electrical Calculators

Wire Sizing Calculator

Select the correct wire gauge for any circuit based on NEC ampacity tables and voltage drop limits.

Calculate Wire Size →

Load Calculation Calculator

Perform NEC Article 220 load calculations for dwelling units, commercial buildings, and feeders.

Calculate Electrical Load →

Conduit Fill Calculator

Calculate conduit fill per NEC Chapter 9 tables. Supports EMT, IMC, RMC, PVC, and flexible conduits.

Calculate Conduit Fill →

Voltage Drop Calculator

Check voltage drop for branch circuits and feeders to stay within NEC recommended limits.

Calculate Voltage Drop →

Wire Ampacity Chart

Interactive NEC Table 310.16 ampacity chart with temperature correction and conduit fill derating.

View Ampacity Chart →

Breaker Size Calculator

Determine the correct overcurrent protection per NEC Article 240, including the 80% continuous load rule.

Calculate Breaker Size →