Wire Size Chart: What Gauge Wire for Every Amperage

Copper and aluminum wire sizes for every common breaker rating from 15 to 200 amps, based on NEC Table 310.16 (75°C) and Table 310.12 for residential services.

Wire Size Chart by Amps

Minimum wire gauge per NEC Table 310.16 at 75°C (THWN/THHN with 75°C-rated terminations). Click an amperage for the full guide.

Amps / BreakerCopper Wire SizeAluminum Wire SizeGuide
15 amp#14 AWG#12 AWG—
20 amp#12 AWG#10 AWG—
30 amp#10 AWG#8 AWG30amp guide →
40 amp#8 AWG#6 AWG40amp guide →
50 amp#6 AWG#4 AWG50amp guide →
60 amp#6 AWG (75°C)#4 AWG60amp guide →
100 amp#3 AWG#1 AWG100amp guide →
125 amp#1 AWG2/0 AWG125amp guide →
150 amp1/0 AWG3/0 AWG150amp guide →
200 amp2/0 AWG (service, 310.12)4/0 AWG (service, 310.12)200amp guide →

15A and 20A limits come from the NEC 240.4(D) small-conductor rule. The 200 amp row shows dwelling-service sizes per Table 310.12; a standard 200A feeder needs 3/0 copper or 250 kcmil aluminum.

60°C, 75°C, and 90°C Columns: Which One Applies?

NEC Table 310.16 lists three ampacities for every wire size, one per insulation temperature rating. You may only use the column matching the lowest temperature rating in the circuit— and that is almost always the terminations, not the wire.

  • 60°C:NM-B cable (Romex) is locked to this column by NEC 334.80, regardless of its 90°C-rated conductors. This is why a 60A circuit in Romex needs #4 copper while the same circuit in conduit needs only #6.
  • 75°C:The working column for most installations — modern breakers, panel lugs, and devices are rated 60/75°C, and THWN/XHHW conductors in conduit qualify. Every recommendation on this page uses the 75°C column.
  • 90°C:THHN's dry-location rating. Used as the starting point for conduit-fill and ambient-temperature derating calculations, but you cannot land a 90°C ampacity on a 75°C lug.

See the full three-column table on the wire ampacity chart.

Copper vs. Aluminum Wire

Aluminum needs roughly two wire sizes largerthan copper for the same ampacity, but still costs about half as much in feeder sizes — which is why virtually every residential service drop and most large feeders are aluminum, while branch circuits stay copper.

Modern AA-8000 alloy aluminum (#8 AWG and larger, typically as SER cable or XHHW-2 in conduit) is safe and code-compliant. The rules that matter: use terminations marked AL/CU, apply antioxidant paste where the manufacturer requires it, and torque lugs to the listed specification. The bad reputation belongs to 1960s small-gauge branch-circuit aluminum, which is a different product entirely.

Wire Size and Voltage Drop

Ampacity tables assume distance doesn't exist. On long runs, resistance steals voltage: the NEC recommends keeping drop under 3% on a branch circuit or feeder (informational notes to 210.19 and 215.2). As a rule of thumb, a 240V circuit loaded to its breaker rating hits 3% around 100 feetat the minimum wire size — and a 120V circuit at only about half that distance.

Past those distances, upsize one gauge per rough doubling of the shortfall — or skip the rules of thumb and use the voltage drop calculator with your actual load and length. Detached garages, well pumps, and RV pads are the classic cases where voltage drop, not ampacity, picks the wire.

Wire Size Guides by Amperage

30 Amp Wire Size: What Gauge Wire Do You Need?

For a 30 amp circuit, use #10 AWG copper or #8 AWG aluminum wire (THWN/THHN rated at 75°C).

Read the Guide →

40 Amp Wire Size: What Gauge Wire Do You Need?

For a 40 amp circuit, use #8 AWG copper or #6 AWG aluminum wire (THWN/THHN rated at 75°C).

Read the Guide →

50 Amp Wire Size: What Gauge Wire Do You Need?

For a 50 amp circuit, use #6 AWG copper or #4 AWG aluminum wire (THWN/THHN rated at 75°C).

Read the Guide →

60 Amp Wire Size: What Gauge Wire Do You Need?

For a 60 amp circuit, use #6 AWG copper (rated 65A at 75°C) or #4 AWG aluminum wire.

Read the Guide →

100 Amp Wire Size: What Gauge Wire Do You Need?

For a 100 amp feeder or circuit, use #3 AWG copper or #1 AWG aluminum wire (THWN/THHN at 75°C).

Read the Guide →

100 Amp Sub Panel Wire Size: What Gauge Feeder Do You Need?

For a 100 amp sub panel, use #3 AWG copper or #1 AWG aluminum feeder conductors with a #8 AWG copper equipment ground (4-wire feeder).

Read the Guide →

125 Amp Wire Size: What Gauge Wire Do You Need?

For a 125 amp circuit or feeder, use #1 AWG copper or 2/0 AWG aluminum wire (THWN/THHN at 75°C).

Read the Guide →

150 Amp Wire Size: What Gauge Wire Do You Need?

For a 150 amp circuit or feeder, use 1/0 AWG copper or 3/0 AWG aluminum wire (THWN/THHN at 75°C).

Read the Guide →

200 Amp Service Wire Size: What Gauge Wire Do You Need?

For a 200 amp residential service, use 2/0 AWG copper or 4/0 AWG aluminum wire (per NEC Table 310.12, the 83% rule for dwelling services).

Read the Guide →

Frequently Asked Questions

What size wire do I need for my amperage?

Match the breaker rating to the NEC Table 310.16 ampacity at 75°C: 15A→#14 copper, 20A→#12, 30A→#10, 40A→#8, 50A→#6, 60A→#6 (75°C terminations), 100A→#3, 125A→#1, 150A→1/0, and 200A→3/0 copper (or 2/0 copper for a dwelling service under Table 310.12). Aluminum runs roughly two sizes larger for the same amperage.

What do the 60°C, 75°C, and 90°C columns mean?

They are insulation temperature ratings. Your usable ampacity is limited by the lowest-rated termination in the circuit — usually 75°C for modern breakers and lugs. The 90°C column (THHN dry rating) is mainly used as a starting point for derating calculations, not for direct breaker sizing. NM-B cable (Romex) is always limited to the 60°C column per NEC 334.80.

Is aluminum wire safe to use?

Modern AA-8000 series aluminum alloy conductors in feeder and service sizes (#8 AWG and larger) are safe and code-compliant, and they cost roughly half as much as copper. The hazards associated with 1960s-era aluminum applied to small branch-circuit wire and old alloys. Use aluminum-rated (AL/CU) terminations and torque them to specification.

When does wire size need to be bigger than the chart says?

Three common cases: long runs (voltage drop — upsize when a 240V run exceeds roughly 100 feet at full load), continuous loads like EV chargers (the circuit must be sized at 125% of a load running 3+ hours), and derating (more than three current-carrying conductors in a conduit, or high ambient temperatures, reduce ampacity per NEC 310.15).

What is the NEC 83% rule (Table 310.12)?

For 120/240V single-phase dwelling services — and feeders that supply the entire dwelling load — NEC 310.12 allows conductors sized at 83% of the service rating, because whole-house loads are diverse and never all run at once. That is why a 200A residential service uses 2/0 copper or 4/0 aluminum instead of the 3/0 copper a standard 200A feeder would need.

Related Electrical Calculators

Wire Sizing Calculator

Calculate the exact gauge for any load, voltage, distance, and conductor material.

Calculate Wire Size →

Voltage Drop Calculator

Find out whether your run length forces a larger wire than ampacity requires.

Calculate Voltage Drop →

Wire Ampacity Chart

Full NEC Table 310.16 at all three temperature columns, copper and aluminum.

View Ampacity Chart →

Breaker Size Calculator

Size the overcurrent device, including the 125% rule for continuous loads.

Size a Breaker →

Conduit Fill Calculator

Check how many conductors fit in each conduit size per NEC Chapter 9.

Calculate Conduit Fill →

Load Calculation

Run an NEC service load calculation before choosing a service or feeder size.

Calculate Load →